Suitable to connect between incoming power
lines and earth terminal at zone intervals LPZ 1 & LPZ 2. Can be
directly connected before the final equipment to be protected.
| Specification |
|
Requirement Class |
Type
2 as per IEC61643 – 1
|
|
Network |
3 Phase TT |
|
Normal
Line Voltage |
230 / 400 volt, 50 – 60 Hz |
|
Nominal Discharge
Current (8/20µS) |
50 KA |
| Voltage Protection
Level |
1200 volt |
|
Response
Time |
L to N < 25 Nano Sec
N to PE < 100 Nano Sec |
|
Degree
of protection |
IP55/65 |
|
Temperature
Range |
- 40 ° C to + 80 ° C |
|
Dimension
in Mm |
H x W x D 253 x 136 x 115 |