For lightning protection equipotentialisation. Suitable
for Class 1 Protection. Can be used as per IEC61024 & 61312. Suitable
to connect between incoming power lines and earth terminal at zone intervals
LPZ 0 & LPZ 1. Device does not require co-ordination cable length
(or Inductor) between class 2 type arrester. Can be used in any telephone
exchange
- Ideal for GSM and Mobile Stations
- Space saving up to 45 %
- No sensitive Electronics and triggering mechanism
inside the arrester
- Fully Encapsulated
| Specification |
| Requirement
Class |
Type 1 as per IEC61643 – 1 |
|
Network |
3 Phase TT |
| Device |
Encapsulated Spark Gap |
| Normal
Line Voltage |
230 / 400 volt, 50 Hz |
| Impulse
Current (10/350µS) |
125 KA |
| Voltage
Protection Level |
1300 volt |
| Response
Time |
< 100 Nano Sec |
| Max.
Series Fuse |
500 A gL/gG (only required if there is no such fuse
already in the network) |
| Degree
of protection |
IP55/65 |
| Temperature
Range |
- 40 ° C to + 70 ° C |
| Dimension
in mm |
H x W x D 253 x 217 x 115 (3 phase) 253 x 136 x 115
|
| Advantages |
1. NO Inductor/Cable Distance required
between the next stage protections
2. Can be used in large networks having a line current up to 500
Amps. |